How do you calculate voltage drop in a wire?
Use Vd = 2 × I × L × R for DC and single-phase circuits, with L the one-way length and R the resistance per unit length. 10 A through 5 m of 14 AWG copper (8.281 Ω/km at 20 °C) drops 828 mV, or 6.9 % of a 12 V supply, and the cable dissipates 8.28 W. For balanced three-phase, replace the 2 with √3.
Voltage drop formula
The drop is the load current times the resistance of the conductors it flows through. The multiplier counts those conductors.
DC and single-phase: Vd = 2 × I × L × z Three-phase: Vd = √3 × I × L × z
- Vd
- voltage drop in V (line-to-line for three-phase)
- I
- load current in A
- L
- one-way length in km
- z
- R for DC, or R cos φ + X sin φ for AC, in Ω/km
Schneider Electric’s Electrical Installation Guide gives the same expression for single-phase and balanced three-phase cables in its Figure G29. The term R cos φ + X sin φ comes from the phasor sum of source voltage, load voltage and the current through the cable’s R + jX. The part of the drop in quadrature with the load voltage is left out, which changes the magnitude very little while the drop is small. With power factor 1 and no reactance the formula is purely resistive.
R (Ω/km) = (1000 × ρ20 / A) × (1 + α20 × (T − 20))
- ρ20
- 1/58 Ω·mm²/m for annealed copper, 0.028264 for EC-H19 aluminum
- α20
- 0.00393 per °C for copper, 0.00403 for aluminum
- A
- cross-section in mm²
The percentage is Vd ÷ source voltage. Power lost is 2 × I² × R × L for two conductors and 3 × I² × R × L for three-phase.
How to calculate voltage drop: worked examples
Example 1: 5 A LED strip on 5 m of 18 AWG at 12 V
18 AWG copper is 20.95 Ω/km at 20 °C. Vd = 2 × 5 × 0.005 × 20.95 = 1.05 V, or 8.73 %. The strip sees 10.95 V and the cable burns 5.24 W. That much drop shows up on an unregulated strip as dimming at the far end, so a thicker feed or a second feed point is worthwhile.
Example 2: smallest wire for 20 A, 10 m at 24 V, 3 % budget
The budget allows 720 mV, so R must be below 720 mV ÷ (2 × 20 A × 0.01 km) = 1.8 Ω/km. The first gauge under that is 7 AWG, at 1.634 Ω/km, which drops 654 mV (2.72 %) and dissipates 13.1 W.
Example 3: 25 A three-phase motor, 80 m of 6 mm²
Stranded copper at 70 °C is 3.507 Ω/km. At power factor 0.85, Vd = √3 × 25 × 0.08 × 3.507 × 0.85 = 10.3 V, which is 2.58 % of 400 V. The three conductors dissipate 526 W.
Voltage drop chart by wire gauge
DC, 10 A over a 10 m one-way run of copper at 20 °C (20 m of conductor). Scale the drop and the loss linearly with length; the drop scales linearly with current and the loss with its square.
| AWG | Area | Resistance | Drop | Cable loss |
|---|
| 4/0 AWG | 107.2 mm² | 0.1608 Ω/km | 32.2 mV | 322 mW |
| 2/0 AWG | 67.43 mm² | 0.2557 Ω/km | 51.1 mV | 511 mW |
| 1/0 AWG | 53.49 mm² | 0.3223 Ω/km | 64.5 mV | 645 mW |
| 2 AWG | 33.62 mm² | 0.5128 Ω/km | 103 mV | 1.03 W |
| 4 AWG | 21.15 mm² | 0.8152 Ω/km | 163 mV | 1.63 W |
| 6 AWG | 13.3 mm² | 1.297 Ω/km | 259 mV | 2.59 W |
| 8 AWG | 8.367 mm² | 2.061 Ω/km | 412 mV | 4.12 W |
| 10 AWG | 5.261 mm² | 3.277 Ω/km | 655 mV | 6.55 W |
| 12 AWG | 3.308 mm² | 5.212 Ω/km | 1.04 V | 10.4 W |
| 14 AWG | 2.082 mm² | 8.281 Ω/km | 1.66 V | 16.6 W |
| 16 AWG | 1.308 mm² | 13.19 Ω/km | 2.64 V | 26.4 W |
| 18 AWG | 0.8229 mm² | 20.95 Ω/km | 4.19 V | 41.9 W |
| 20 AWG | 0.5189 mm² | 33.23 Ω/km | 6.65 V | 66.5 W |
| 22 AWG | 0.3243 mm² | 53.16 Ω/km | 10.6 V | 106 W |
| 24 AWG | 0.2047 mm² | 84.22 Ω/km | 16.8 V | 168 W |
| 26 AWG | 0.1281 mm² | 134.6 Ω/km | 26.9 V | 269 W |
Longest run for a 3 % drop at 10 A
One-way length in meters for DC or single-phase at 20 °C on copper. Multiply by 3.281 for feet. Length scales inversely with current.
| AWG | 5 V | 12 V | 24 V | 48 V | 120 V |
|---|
| 2 AWG | 14.6 m | 35.1 m | 70.2 m | 140 m | 351 m |
| 4 AWG | 9.2 m | 22.1 m | 44.2 m | 88.3 m | 221 m |
| 6 AWG | 5.78 m | 13.9 m | 27.8 m | 55.5 m | 139 m |
| 8 AWG | 3.64 m | 8.74 m | 17.5 m | 34.9 m | 87.4 m |
| 10 AWG | 2.29 m | 5.49 m | 11 m | 22 m | 54.9 m |
| 12 AWG | 1.44 m | 3.45 m | 6.91 m | 13.8 m | 34.5 m |
| 14 AWG | 0.906 m | 2.17 m | 4.35 m | 8.69 m | 21.7 m |
| 16 AWG | 0.569 m | 1.37 m | 2.73 m | 5.46 m | 13.7 m |
| 18 AWG | 0.358 m | 0.859 m | 1.72 m | 3.44 m | 8.59 m |
| 20 AWG | 0.226 m | 0.542 m | 1.08 m | 2.17 m | 5.42 m |
Where the simple model stops
The calculation assumes the current stays fixed. A switching regulator draws more current as its input sags, so near its minimum input a real drop is worse than computed. Connectors, fuses and crimps add resistance that the cable table does not count, and at low voltage they can matter as much as the wire. Use a realistic conductor temperature: a cable near its rating runs far above 20 °C. Voltage drop and heating are separate limits, so a wire that passes this check still needs an ampacity check. Metric sizes use the nominal area: IEC 60228 also sets resistance limits for each size and a real cable can measure higher, so take the resistance from the data sheet when the budget is tight. For large AC cables, enter the reactance from the data sheet, and treat the DC resistance as a lower bound because skin and proximity effects raise the AC value.
Glossary
- Voltage drop
- The voltage lost along the conductors between the source and the load.
- One-way length
- The cable distance from source to load, not counting the return conductor.
- k-factor
- Resistance of a conductor one circular mil in area and one foot long: 12.9 for copper and 21.2 for aluminum at 75 °C in NEC practice.
- Power factor
- cos φ, where φ is the angle between load voltage and current. Motors typically run below 1.
- Reactance (X)
- The inductive part of a cable’s AC impedance. It depends mainly on conductor spacing, and matters most for large cables.
- Line-to-line voltage
- The voltage between two phases of a three-phase system, 400 V in a 230/400 V supply.
Frequently asked questions
What is the formula for voltage drop in a wire?
For DC and single-phase AC, the voltage drop equation is Vd = 2 × I × L × R, where L is the one-way length and R is the resistance per unit length: the 2 covers the out and back conductors. For balanced three-phase, the 2 becomes √3, and Vd is the line-to-line drop.
Is the cable length one way or round trip?
Enter the one-way distance from source to load. The calculator adds the return path, so 5 m of cable means 10 m of conductor in a DC or single-phase circuit.
How much voltage drop is acceptable?
It depends on what the load tolerates. The NEC mentions voltage drop for most circuits only in informational notes, which are not mandatory, and the IAEI describes 5 % as the maximum generally suggested for a circuit; 3 % is a common design target. Low-voltage electronics often need less, so work back from the load’s minimum input voltage.
What is the voltage drop for 10 A over 5 m of 14 AWG?
828 mV at 20 °C, which is 6.9 % of a 12 V supply. The cable dissipates 8.28 W.
Does wire temperature change voltage drop?
Yes. Copper’s resistance rises about 0.393 % per °C from 20 °C, so a conductor at 75 °C has 1.216 times the 20 °C resistance. NEC table values are quoted at 75 °C for that reason.
Why is the three-phase multiplier √3 and not 2?
In a balanced three-phase circuit the phase currents sum to zero, so no current returns on a neutral and each line drops I × R to its load. Line-to-line voltage is the difference of two phases 120° apart, which is √3 times the per-phase drop.
How do I reduce voltage drop?
Use a thicker wire, shorten the run, raise the supply voltage so the same power needs less current, or run conductors in parallel. Doubling the voltage at constant power halves the current and cuts the percentage drop to a quarter.
Does this work as a volt drop calculator or a voltage loss calculator?
Yes. Volt drop, voltage loss and voltage drop all name the voltage lost along the conductors between the source and the load. The cable’s power loss is shown next to it.
More free PCB tools
See all free electronics tools →
- Transformer calculatorTurns ratio, secondary voltage and current, reflected impedance and VA rating for an ideal transformer.
- Supercapacitor calculatorHold-up time of a supercapacitor at constant power or current between two voltages, including ESR drop, or the size you need.
- Power factor calculatorReal, reactive and apparent power and power factor, and the capacitor that corrects it to a target power factor.
- 3 phase power calculatorReal, apparent and reactive power, line and phase current for three-phase star or delta loads.
- Online KiCad design checkerUpload a KiCad project to run KiCad 10 DRC, ERC and schematic parity, plus JLCPCB or PCBWay rules. Every finding links to its fix.
- AI circuit diagram makerDescribe a circuit in plain English and get a clean schematic with standard symbols and a checked netlist. Export SVG, PNG, PDF, KiCad or SPICE.
Sources
- Schneider Electric, Electrical Installation Guide, Calculation of voltage drop in steady load conditions, Figure G29 (R cos φ + X sin φ with the 2 and √3 multipliers)
- IAEI Magazine, Voltage Drop Calculations (2 and 1.732 multipliers, k-factor method, NEC informational notes)
- NBS Handbook 100, Copper Wire Tables (AWG sizes, copper resistivity, temperature coefficient, stranding)
- NBS Handbook 109, Aluminum Wire Tables (EC-H19 aluminum)
- NASA EEE-INST-002, Section W1, Table 4A (derated wire current used for the heating warning)
- IEC 60228, Conductors of insulated cables (metric nominal sizes)