Power factor calculator

Start from whatever you can measure. This power factor calculator returns the real, reactive and apparent power and the power factor, on single-phase or three-phase systems, then sizes the capacitor that corrects the load to your target, in kvar and in microfarads.

What you know
Examples
System
V

RMS. Line-to-line if three-phase.

A

RMS. Line current if three-phase.

Lagging, above 0 up to 1.

Optional: sizes the correction capacitor.

Hz
V

Optional: output scales with V², so a higher-rated part delivers less at this supply.

VA

Optional: gives the harmonic the bank resonates at. A transformer alone is about kVA ÷ per-unit impedance.

Real power P

3.6 kW

Apparent power S
4.8 kVA
Reactive power Q
3.175 kvar
Power factor
0.75
Phase angle φ
41.41 °
kvar per kW (tan φ)
0.8819
Capacitor Qc to reach PF 0.95
1.992 kvar
Multiplier (tan φ1 − tan φ2)
0.553 kvar per kW
Capacitance
91.72 µF across 240 V
Capacitor current
8.298 A
Current after
15.79 A 21.1 % less
Apparent power after
3.789 kVA
I²R loss saved upstream
37.7 %

Assumes sinusoidal voltage and current and a lagging (inductive) load, the case shunt capacitors correct.

Capacitor needed and line current versus target power factor
05001k1.5k2k2.5k3k3.5k051015200.750.80.850.90.951Target power factorCapacitor (var)Current (A)PF 0.95
Capacitor (var)Line current (A)

Correction to common target power factors

Target PFkvar per kWCapacitorCapacitanceCurrent afterI²R loss saved
0.850.262944 var43.5 µF17.6 A22.1 %
0.900.3981.43 kvar65.9 µF16.7 A30.6 %
0.920.4561.64 kvar75.6 µF16.3 A33.5 %
0.950.5531.99 kvar91.7 µF15.8 A37.7 %
0.970.6312.27 kvar105 µF15.5 A40.2 %
0.980.6792.44 kvar113 µF15.3 A41.4 %
1.000.8823.17 kvar146 µF15 A43.8 %

What is the power factor formula?

Divide real power by apparent power. The power factor equation is PF = P ÷ S, which equals cos φ for sinusoidal waveforms. A 240 V, 20 A load drawing 3.6 kW has S = 4.8 kVA, so PF = 0.75, and it carries Q = 3.17 kvar of reactive power. Raising it to 0.95 takes a capacitor of Qc = P × (tan φ1 − tan φ2) = 1.99 kvar, which is 91.7 µF at 240 V and 60 Hz.

Power factor formula and the power triangle

Real, reactive and apparent power form a right triangle. Real power P is the adjacent side, reactive power Q the opposite side, apparent power S the hypotenuse, and φ the angle between voltage and current.

S = V × I (single-phase)     S = √3 × V × I (three-phase)
S
apparent power in VA
P
real power in W
Q
reactive power in var
V, I
RMS voltage and current (line-to-line voltage and line current for three-phase)
φ
phase angle between voltage and current
PF = P ÷ S = cos φ     Q = √(S² − P²) = P × tan φ

A shunt capacitor supplies reactive power locally, so the source no longer has to. The capacitor needed to move from φ1 to φ2 at constant real power is the same for single-phase and three-phase systems:

Qc = P × (tan φ1 − tan φ2)

The capacitance follows from Q = 2π f C V² applied to each capacitor and the voltage it sees:

Single-phase: C = Qc ÷ (2π f V²)
Three-phase delta, per phase: C = Qc ÷ (3 × 2π f VL²)
Three-phase star, per phase: C = Qc ÷ (2π f VL²)

At constant real power the current is inversely proportional to the power factor, and the I²R loss upstream of the capacitor follows the square of the current:

I2 = I1 × (PF1 ÷ PF2)     Loss saved = 1 − (PF1 ÷ PF2)²

Power factor calculation examples

Example 1: a 240 V, 20 A single-phase motor at PF 0.75

S = 240 × 20 = 4.8 kVA. P = S × 0.75 = 3.6 kW. Q = √(S² − P²) = 3.17 kvar. The angle is 41.4°.

To reach PF 0.95, the multiplier is 0.553, so Qc = 1.99 kvar and C = Qc ÷ (2π × 60 × 240²) = 91.7 µF. The current drops from 20 A to 15.8 A.

Example 2: a 410 kW plant from 0.73 to 0.95 at 480 V

This is the example in Eaton’s guide, which reads a multiplier of 0.607 from its table. The formula gives 0.608, so Qc = 249 kvar and Eaton rounds up to a 250 kvar bank. At 480 V and 60 Hz, delta capacitors would be 956 µF per phase. The bank draws 300 A, and the plant’s line current falls from 676 A to 519 A.

Example 3: star or delta for 300 kW at 400 V, 50 Hz

Going from PF 0.8 to 0.93 takes Qc = 106 kvar (ABB’s worked example rounds tan φ2 to 0.39 and gets 108 kvar). Line current drops from 541 A to 466 A.

In delta each capacitor is 706 µF across 400 V. In star each is 2.12 mF across 231 V: three times the capacitance at a lower voltage, for the same kvar.

Power factor correction table: capacitor kvar multipliers

Multiply the load in kW by the value here to get the capacitor kvar. Each entry is tan φ1 − tan φ2, and matches published multiplier tables to within rounding.

Present PF \ Target0.850.900.920.950.970.981.00
0.501.1121.2481.3061.4031.4811.5291.732
0.550.8991.0341.0921.1901.2681.3151.518
0.600.7140.8490.9071.0051.0831.1301.333
0.650.5490.6850.7430.8400.9190.9661.169
0.700.4000.5360.5940.6920.7700.8171.020
0.750.2620.3980.4560.5530.6310.6790.882
0.800.1300.2660.3240.4210.4990.5470.750
0.85–0.1350.1940.2910.3690.4170.620
0.90––0.0580.1560.2340.2810.484
0.95––––0.0780.1260.329

kvar to microfarads table: µF and amps per kvar

The first two columns are the capacitance across the stated voltage: single-phase, or the total of a delta bank. The delta columns are each of the three capacitors. Multiply by the kvar you need.

VoltageµF/kvar, 60 HzµF/kvar, 50 HzDelta µF per phase, 60 HzDelta µF per phase, 50 HzA/kvar, 1-phaseA/kvar, 3-phase
120 V184221––8.33–
208 V61.373.620.424.54.812.78
240 V46.155.315.418.44.172.41
400 V16.619.95.536.632.51.44
415 V15.418.55.136.162.411.39
480 V11.513.83.844.612.081.2
600 V7.378.842.462.951.670.962

Typical power factor by load

Starting points from ABB’s Technical Application Paper No. 8, Table 1.1. Measure your own load when you can.

LoadPower factor
Transformer, no load0.1 to 0.15
Motor0.7 to 0.85
Arc welding0.35 to 0.6
Arc welding, compensated0.7 to 0.8
Resistance welding0.4 to 0.6
Arc melting furnace0.75 to 0.9
Fluorescent lamps, compensated0.9
Fluorescent lamps, uncompensated0.4 to 0.6
AC to DC converters0.6 to 0.95
DC drives0.4 to 0.75
AC drives0.95 to 0.97
Resistive load1

What goes wrong in real installations

The formulas assume sinusoidal waveforms and a steady load. Check these before ordering a bank.

  • Capacitor voltage rating. Output scales with voltage squared and in proportion to frequency: Eaton’s example is 10 kvar at 240 V delivering 7.5 kvar at 208 V, and a 60 Hz rating giving 83 % at 50 Hz. Enter the rated voltage above to get the nameplate kvar to order.
  • Motors. A capacitor switched with a motor can self-excite it as a generator after disconnection. Do not exceed the motor maker’s maximum kvar; ABB’s rule is no more than 90 % of the motor’s no-load reactive power.
  • Harmonics and resonance. A shunt bank resonates with the source inductance near h = √(short-circuit kVA ÷ kvar). Eaton’s example of 17,391 kVA with 350 kvar gives h = 7.05, right on the 7th harmonic, so that bank should be a harmonic filter. The risk grows as more kvar is added to a system with a significant nonlinear load.
  • Varying load. A fixed bank sized for full load can overcorrect at light load, push the power factor leading and raise the voltage. Use automatic switched steps when the load swings.
  • Current rating. Eaton’s conductor table uses 135 % of rated current, following NEC Article 460. ABB derives 1.43 × rated current for banks up to 100 kvar and 1.365 × above that, from IEC 60831-1 overcurrent and capacitance tolerance limits.
  • Stored charge. Capacitors stay charged after disconnection. The limit depends on the code: Eaton lists under 50 V within 1 minute for capacitors rated 600 V and below, and ABB quotes IEC 60831-1 as 75 V or less within 3 minutes. Verify with a meter before touching the terminals.

Glossary

Real power (P)
The power that does work or makes heat, in watts.
Reactive power (Q)
Power exchanged back and forth with magnetic and electric fields, in var. It does no net work but its current still flows in the wiring.
Apparent power (S)
V × I (√3 × V × I for three-phase), in VA. Cables and transformers must carry this.
Power factor (PF)
P ÷ S, from 0 to 1. Equal to cos φ for sinusoidal waveforms.
Lagging
Current behind voltage, as in motors and transformers. Shunt capacitors correct it.
Displacement power factor
cos φ of the fundamental only, ignoring harmonics.
kvar multiplier
tan φ1 − tan φ2: the kvar of capacitor per kW of load for a given correction.
Parallel resonance
The frequency where a shunt capacitor bank and the source inductance resonate, which can amplify harmonics.

Related guides

Frequently asked questions

How do I calculate power factor from watts, volts and amps?

Divide real power by apparent power: PF = W ÷ (V × A) on a single-phase circuit, and PF = W ÷ (√3 × V × A) on a three-phase circuit with line-to-line voltage and line current. A load reading 600 W at 120 V and 8 A has PF = 600 ÷ 960 = 0.625. The V, I and P mode of this PF calculator takes those three readings directly.

What are the apparent power and reactive power formulas?

The apparent power formula is S = V × I on single-phase and S = √3 × V × I on three-phase. The reactive power formula is Q = √(S² − P²) = P × tan φ. With real power P they form the power triangle.

How do I convert kW to kVA?

Divide kW by the power factor: S = P ÷ PF. 300 kW at PF 0.8 is 375 kVA. Choose P and PF at the top of the calculator to get this directly.

How many kvar do I need to correct power factor?

The power factor correction formula is Qc = P × (tan φ1 − tan φ2), where φ1 and φ2 are the angles of the present and target power factors. A 100 kW load going from 0.80 to 0.95 needs 42.1 kvar. Tables of "kvar per kW" multipliers are this same formula, printed.

How do I convert kvar to microfarads?

C = Q ÷ (2π f V²) for a capacitor across voltage V. At 240 V and 60 Hz, 1 kvar is 46.1 µF. In a three-phase delta bank each capacitor sees the line voltage and supplies a third of the kvar, so 1 kvar at 480 V and 60 Hz is 3.84 µF per phase.

What is a good power factor?

About 0.95 is the usual target: Eaton notes that correcting to approximately 95 % gives the maximum practical benefit. Tariffs vary, but ABB describes a typical arrangement where reactive energy is charged for power factors from 0.7 to 0.9 and nothing is due above 0.9.

Should I correct power factor all the way to 1.0?

Usually not. Going from 0.80 to 0.95 on 100 kW takes 42.1 kvar, while reaching 1.00 takes 75 kvar for a small further drop in current, and a fixed bank at unity turns leading as soon as the load falls.

Is power factor the same as cos φ?

Only for sinusoidal voltage and current. With harmonics, the total power factor P ÷ S equals cos φ of the fundamental multiplied by a distortion factor, so a drive or rectifier can have a good cos φ and a poor total power factor. Capacitors supply reactive power only, so they do not remove the distortion.

Does power factor correction save energy?

It does not change the real power the load uses. It lowers the current upstream of the capacitor, and with it the I²R loss in cables and transformers: going from 0.75 to 0.95 cuts that loss by 37.7 %. Where the tariff bills kVA demand or reactive energy, those charges fall too.

Should a three-phase capacitor bank be star or delta?

For the same kvar a star bank needs three times the capacitance per phase, but each capacitor sees only VL ÷ √3. At low voltage, delta is usually preferred because the capacitors are smaller.