What is the power factor formula?
Divide real power by apparent power. The power factor equation is PF = P ÷ S, which equals cos φ for sinusoidal waveforms. A 240 V, 20 A load drawing 3.6 kW has S = 4.8 kVA, so PF = 0.75, and it carries Q = 3.17 kvar of reactive power. Raising it to 0.95 takes a capacitor of Qc = P × (tan φ1 − tan φ2) = 1.99 kvar, which is 91.7 µF at 240 V and 60 Hz.
Power factor formula and the power triangle
Real, reactive and apparent power form a right triangle. Real power P is the adjacent side, reactive power Q the opposite side, apparent power S the hypotenuse, and φ the angle between voltage and current.
S = V × I (single-phase) S = √3 × V × I (three-phase)
- S
- apparent power in VA
- P
- real power in W
- Q
- reactive power in var
- V, I
- RMS voltage and current (line-to-line voltage and line current for three-phase)
- φ
- phase angle between voltage and current
PF = P ÷ S = cos φ Q = √(S² − P²) = P × tan φ
A shunt capacitor supplies reactive power locally, so the source no longer has to. The capacitor needed to move from φ1 to φ2 at constant real power is the same for single-phase and three-phase systems:
Qc = P × (tan φ1 − tan φ2)
The capacitance follows from Q = 2π f C V² applied to each capacitor and the voltage it sees:
Single-phase: C = Qc ÷ (2π f V²)
Three-phase delta, per phase: C = Qc ÷ (3 × 2π f VL²)
Three-phase star, per phase: C = Qc ÷ (2π f VL²)
At constant real power the current is inversely proportional to the power factor, and the I²R loss upstream of the capacitor follows the square of the current:
I2 = I1 × (PF1 ÷ PF2) Loss saved = 1 − (PF1 ÷ PF2)²
Power factor calculation examples
Example 1: a 240 V, 20 A single-phase motor at PF 0.75
S = 240 × 20 = 4.8 kVA. P = S × 0.75 = 3.6 kW. Q = √(S² − P²) = 3.17 kvar. The angle is 41.4°.
To reach PF 0.95, the multiplier is 0.553, so Qc = 1.99 kvar and C = Qc ÷ (2π × 60 × 240²) = 91.7 µF. The current drops from 20 A to 15.8 A.
Example 2: a 410 kW plant from 0.73 to 0.95 at 480 V
This is the example in Eaton’s guide, which reads a multiplier of 0.607 from its table. The formula gives 0.608, so Qc = 249 kvar and Eaton rounds up to a 250 kvar bank. At 480 V and 60 Hz, delta capacitors would be 956 µF per phase. The bank draws 300 A, and the plant’s line current falls from 676 A to 519 A.
Example 3: star or delta for 300 kW at 400 V, 50 Hz
Going from PF 0.8 to 0.93 takes Qc = 106 kvar (ABB’s worked example rounds tan φ2 to 0.39 and gets 108 kvar). Line current drops from 541 A to 466 A.
In delta each capacitor is 706 µF across 400 V. In star each is 2.12 mF across 231 V: three times the capacitance at a lower voltage, for the same kvar.
Power factor correction table: capacitor kvar multipliers
Multiply the load in kW by the value here to get the capacitor kvar. Each entry is tan φ1 − tan φ2, and matches published multiplier tables to within rounding.
| Present PF \ Target | 0.85 | 0.90 | 0.92 | 0.95 | 0.97 | 0.98 | 1.00 |
|---|
| 0.50 | 1.112 | 1.248 | 1.306 | 1.403 | 1.481 | 1.529 | 1.732 |
| 0.55 | 0.899 | 1.034 | 1.092 | 1.190 | 1.268 | 1.315 | 1.518 |
| 0.60 | 0.714 | 0.849 | 0.907 | 1.005 | 1.083 | 1.130 | 1.333 |
| 0.65 | 0.549 | 0.685 | 0.743 | 0.840 | 0.919 | 0.966 | 1.169 |
| 0.70 | 0.400 | 0.536 | 0.594 | 0.692 | 0.770 | 0.817 | 1.020 |
| 0.75 | 0.262 | 0.398 | 0.456 | 0.553 | 0.631 | 0.679 | 0.882 |
| 0.80 | 0.130 | 0.266 | 0.324 | 0.421 | 0.499 | 0.547 | 0.750 |
| 0.85 | – | 0.135 | 0.194 | 0.291 | 0.369 | 0.417 | 0.620 |
| 0.90 | – | – | 0.058 | 0.156 | 0.234 | 0.281 | 0.484 |
| 0.95 | – | – | – | – | 0.078 | 0.126 | 0.329 |
kvar to microfarads table: µF and amps per kvar
The first two columns are the capacitance across the stated voltage: single-phase, or the total of a delta bank. The delta columns are each of the three capacitors. Multiply by the kvar you need.
| Voltage | µF/kvar, 60 Hz | µF/kvar, 50 Hz | Delta µF per phase, 60 Hz | Delta µF per phase, 50 Hz | A/kvar, 1-phase | A/kvar, 3-phase |
|---|
| 120 V | 184 | 221 | – | – | 8.33 | – |
| 208 V | 61.3 | 73.6 | 20.4 | 24.5 | 4.81 | 2.78 |
| 240 V | 46.1 | 55.3 | 15.4 | 18.4 | 4.17 | 2.41 |
| 400 V | 16.6 | 19.9 | 5.53 | 6.63 | 2.5 | 1.44 |
| 415 V | 15.4 | 18.5 | 5.13 | 6.16 | 2.41 | 1.39 |
| 480 V | 11.5 | 13.8 | 3.84 | 4.61 | 2.08 | 1.2 |
| 600 V | 7.37 | 8.84 | 2.46 | 2.95 | 1.67 | 0.962 |
Typical power factor by load
Starting points from ABB’s Technical Application Paper No. 8, Table 1.1. Measure your own load when you can.
| Load | Power factor |
|---|
| Transformer, no load | 0.1 to 0.15 |
| Motor | 0.7 to 0.85 |
| Arc welding | 0.35 to 0.6 |
| Arc welding, compensated | 0.7 to 0.8 |
| Resistance welding | 0.4 to 0.6 |
| Arc melting furnace | 0.75 to 0.9 |
| Fluorescent lamps, compensated | 0.9 |
| Fluorescent lamps, uncompensated | 0.4 to 0.6 |
| AC to DC converters | 0.6 to 0.95 |
| DC drives | 0.4 to 0.75 |
| AC drives | 0.95 to 0.97 |
| Resistive load | 1 |
What goes wrong in real installations
The formulas assume sinusoidal waveforms and a steady load. Check these before ordering a bank.
- Capacitor voltage rating. Output scales with voltage squared and in proportion to frequency: Eaton’s example is 10 kvar at 240 V delivering 7.5 kvar at 208 V, and a 60 Hz rating giving 83 % at 50 Hz. Enter the rated voltage above to get the nameplate kvar to order.
- Motors. A capacitor switched with a motor can self-excite it as a generator after disconnection. Do not exceed the motor maker’s maximum kvar; ABB’s rule is no more than 90 % of the motor’s no-load reactive power.
- Harmonics and resonance. A shunt bank resonates with the source inductance near h = √(short-circuit kVA ÷ kvar). Eaton’s example of 17,391 kVA with 350 kvar gives h = 7.05, right on the 7th harmonic, so that bank should be a harmonic filter. The risk grows as more kvar is added to a system with a significant nonlinear load.
- Varying load. A fixed bank sized for full load can overcorrect at light load, push the power factor leading and raise the voltage. Use automatic switched steps when the load swings.
- Current rating. Eaton’s conductor table uses 135 % of rated current, following NEC Article 460. ABB derives 1.43 × rated current for banks up to 100 kvar and 1.365 × above that, from IEC 60831-1 overcurrent and capacitance tolerance limits.
- Stored charge. Capacitors stay charged after disconnection. The limit depends on the code: Eaton lists under 50 V within 1 minute for capacitors rated 600 V and below, and ABB quotes IEC 60831-1 as 75 V or less within 3 minutes. Verify with a meter before touching the terminals.
Glossary
- Real power (P)
- The power that does work or makes heat, in watts.
- Reactive power (Q)
- Power exchanged back and forth with magnetic and electric fields, in var. It does no net work but its current still flows in the wiring.
- Apparent power (S)
- V × I (√3 × V × I for three-phase), in VA. Cables and transformers must carry this.
- Power factor (PF)
- P ÷ S, from 0 to 1. Equal to cos φ for sinusoidal waveforms.
- Lagging
- Current behind voltage, as in motors and transformers. Shunt capacitors correct it.
- Displacement power factor
- cos φ of the fundamental only, ignoring harmonics.
- kvar multiplier
- tan φ1 − tan φ2: the kvar of capacitor per kW of load for a given correction.
- Parallel resonance
- The frequency where a shunt capacitor bank and the source inductance resonate, which can amplify harmonics.
Frequently asked questions
How do I calculate power factor from watts, volts and amps?
Divide real power by apparent power: PF = W ÷ (V × A) on a single-phase circuit, and PF = W ÷ (√3 × V × A) on a three-phase circuit with line-to-line voltage and line current. A load reading 600 W at 120 V and 8 A has PF = 600 ÷ 960 = 0.625. The V, I and P mode of this PF calculator takes those three readings directly.
What are the apparent power and reactive power formulas?
The apparent power formula is S = V × I on single-phase and S = √3 × V × I on three-phase. The reactive power formula is Q = √(S² − P²) = P × tan φ. With real power P they form the power triangle.
How do I convert kW to kVA?
Divide kW by the power factor: S = P ÷ PF. 300 kW at PF 0.8 is 375 kVA. Choose P and PF at the top of the calculator to get this directly.
How many kvar do I need to correct power factor?
The power factor correction formula is Qc = P × (tan φ1 − tan φ2), where φ1 and φ2 are the angles of the present and target power factors. A 100 kW load going from 0.80 to 0.95 needs 42.1 kvar. Tables of "kvar per kW" multipliers are this same formula, printed.
How do I convert kvar to microfarads?
C = Q ÷ (2π f V²) for a capacitor across voltage V. At 240 V and 60 Hz, 1 kvar is 46.1 µF. In a three-phase delta bank each capacitor sees the line voltage and supplies a third of the kvar, so 1 kvar at 480 V and 60 Hz is 3.84 µF per phase.
What is a good power factor?
About 0.95 is the usual target: Eaton notes that correcting to approximately 95 % gives the maximum practical benefit. Tariffs vary, but ABB describes a typical arrangement where reactive energy is charged for power factors from 0.7 to 0.9 and nothing is due above 0.9.
Should I correct power factor all the way to 1.0?
Usually not. Going from 0.80 to 0.95 on 100 kW takes 42.1 kvar, while reaching 1.00 takes 75 kvar for a small further drop in current, and a fixed bank at unity turns leading as soon as the load falls.
Is power factor the same as cos φ?
Only for sinusoidal voltage and current. With harmonics, the total power factor P ÷ S equals cos φ of the fundamental multiplied by a distortion factor, so a drive or rectifier can have a good cos φ and a poor total power factor. Capacitors supply reactive power only, so they do not remove the distortion.
Does power factor correction save energy?
It does not change the real power the load uses. It lowers the current upstream of the capacitor, and with it the I²R loss in cables and transformers: going from 0.75 to 0.95 cuts that loss by 37.7 %. Where the tariff bills kVA demand or reactive energy, those charges fall too.
Should a three-phase capacitor bank be star or delta?
For the same kvar a star bank needs three times the capacitance per phase, but each capacitor sees only VL ÷ √3. At low voltage, delta is usually preferred because the capacitors are smaller.
More free PCB tools
See all free electronics tools →
- 3 phase power calculatorReal, apparent and reactive power, line and phase current for three-phase star or delta loads.
- Transformer calculatorTurns ratio, secondary voltage and current, reflected impedance and VA rating for an ideal transformer.
- Supercapacitor calculatorHold-up time of a supercapacitor at constant power or current between two voltages, including ESR drop, or the size you need.
- Wire voltage drop calculatorVoltage drop and power loss along a cable from its gauge, length, current and material, and the gauge that keeps drop in budget.
- Online KiCad design checkerUpload a KiCad project to run KiCad 10 DRC, ERC and schematic parity, plus JLCPCB or PCBWay rules. Every finding links to its fix.
- AI circuit diagram makerDescribe a circuit in plain English and get a clean schematic with standard symbols and a checked netlist. Export SVG, PNG, PDF, KiCad or SPICE.
Design the whole board, not one number
ProtoFlow is free AI PCB design software: describe a circuit and get a schematic with real parts, PCB layout with an autorouter, SPICE simulation and Gerber files. Native KiCad, Altium and EAGLE import and export. Free on macOS, Windows and Linux.