3 phase power calculator

From line voltage, current and power factor, this 3 phase power calculator gives real, apparent and reactive power. Start from a load in kW or kVA instead and it finds the line current. See the voltage and current on each element for star or delta loads, and what the same load draws on common system voltages.

Solve for
Examples
V

RMS, between two phases. On a 120/208 V system enter 208.

A

Above 0 up to 1.

Connection

Total real power P

70.67 kW

Apparent power S
83.14 kVA
Reactive power Q
43.8 kvar
Power factor
0.85
Phase angle φ
31.79 °
Line current
100 A
Line-to-line voltage
480 V
Voltage across each element
277.1 V VL / √3 (line-to-neutral)
Current through each element
100 A IL
Power per phase
23.56 kW
Equivalent |Z| per element
2.771 Ω
Equivalent R per element
2.356 Ω
Equivalent X per element
1.46 Ω

Assumes a balanced load and sinusoidal voltages. For an unbalanced load, work out each phase separately and add the powers.

For the same line voltage, line current and power factor, total power is identical in star and delta. The connection only changes what each element sees.

Line current versus power factor for 70.7 kW at 480 V
0501001502002500.40.50.60.70.80.91Power factorLine current (A)PF 0.85

The same 70.7 kW at PF 0.85 on common systems

Line voltageLine currentStar: V per elementDelta: I per element
208 V230.8 A120.1 V133.2 A
240 V200 A138.6 V115.5 A
400 V120 A230.9 V69.28 A
415 V115.7 A239.6 V66.78 A
480 V100 A277.1 V57.74 A
600 V80 A346.4 V46.19 A
690 V69.57 A398.4 V40.16 A

How do you calculate three-phase power?

Use P = √3 × VL × IL × PF, with line-to-line voltage, line current and power factor. At 480 V, 100 A and PF 0.85, real power is 70.7 kW, apparent power is 83.1 kVA and reactive power is 43.8 kvar. To go the other way, line current is I = P ÷ (√3 × VL × PF). The result is the same whether the load is connected in star or delta.

3 phase power formula: kW, kVA, kvar and line current

These hold for a balanced load with sinusoidal voltages, using RMS line-to-line voltage and line current. The results are totals for all three phases.

P = √3 × VL × IL × PF     S = √3 × VL × IL     Q = √(S² − P²)
P
total real power in W
S
total apparent power in VA
Q
total reactive power in var
VL
line-to-line voltage in V
IL
line current in A
PF
power factor, cos φ

Solved for the line current:

IL = P ÷ (√3 × VL × PF)     IL = S ÷ (√3 × VL)

What each element of the load sees depends on how the three are connected:

Star (wye): Vph = VL ÷ √3    Iph = IL
Delta: Vph = VL    Iph = IL ÷ √3

From the impedance Z = R + jX of each element, per-phase Ohm’s law gives everything else:

Iph = Vph ÷ |Z|     P = 3 × Iph² × R     Q = 3 × Iph² × X     PF = R ÷ |Z|

3 phase power calculation examples

Example 1: 480 V, 100 A at PF 0.85

S = √3 × 480 × 100 = 83.1 kVA. P = S × 0.85 = 70.7 kW. Q = √(S² − P²) = 43.8 kvar. In a star load each element sees 277.1 V and carries the full 100 A. In delta each would see 480 V and carry 57.74 A.

Example 2: line current of 170 kW at 400 V

At PF 0.7, I = 170,000 ÷ (√3 × 400 × 0.7) = 350.5 A. Correcting to PF 0.9 brings it to 272.6 A for the same real power. ABB uses this case to show the cable dropping from 120 mm² to 70 mm².

Example 3: a 6 kW heater on a 120/208 V supply

Three 2 kW elements. In star each sees 120.1 V, so R = 120² ÷ 2000 = 7.2 Ω and the heater draws 6.01 kW at 16.68 A per line. In delta each sees 208 V, so R = 208² ÷ 2000 = 21.6 Ω, three times larger, for 6.01 kW and the same 16.68 A line current.

Wire the 7.2 Ω elements in delta by mistake and each sees 208 V: the heater draws 18 kW at 50.04 A, three times the design.

3 phase kVA to amps table

Line current I = S ÷ (√3 × VL) for common kVA sizes and system voltages. Power factor does not affect this figure. For sizes not listed, use the 3 phase calculator at the top of the page.

kVA208 V240 V400 V415 V480 V600 V
1541.64 A36.08 A21.65 A20.87 A18.04 A14.43 A
3083.27 A72.17 A43.3 A41.74 A36.08 A28.87 A
45124.9 A108.3 A64.95 A62.6 A54.13 A43.3 A
75208.2 A180.4 A108.3 A104.3 A90.21 A72.17 A
112.5312.3 A270.6 A162.4 A156.5 A135.3 A108.3 A
150416.4 A360.8 A216.5 A208.7 A180.4 A144.3 A
225624.5 A541.3 A324.8 A313 A270.6 A216.5 A
300832.7 A721.7 A433 A417.4 A360.8 A288.7 A
5001388 A1203 A721.7 A695.6 A601.4 A481.1 A
7502082 A1804 A1083 A1043 A902.1 A721.7 A
10002776 A2406 A1443 A1391 A1203 A962.3 A

3 phase kW to amps table by voltage and power factor

Amps per kW: multiply by the load in kW. A lower power factor needs more current for the same real power. The three-phase current calculator at the top takes kW or kVA directly.

VoltagePF 1.00PF 0.95PF 0.90PF 0.85PF 0.80PF 0.70
208 V2.782.923.083.273.473.97
240 V2.412.532.672.833.013.44
400 V1.441.521.61.71.82.06
415 V1.391.461.551.641.741.99
480 V1.21.271.341.421.51.72
600 V0.9621.011.071.131.21.37

Star versus delta: the same elements on the same supply

Three 10 Ω resistive elements on a 400 V supply, computed both ways.

QuantityStarDelta
Voltage across each element230.9 V400 V
Current through each element23.09 A40 A
Line current23.09 A69.28 A
Total power16 kW48 kW

Common three-phase system voltages

Nominal values from IEC 60038 Table 1, written line-to-neutral / line-to-line. The nominal pairs are rounded, so dividing VL by √3 lands close to the first number. Three-wire 240 V, 480 V and 600 V systems at 60 Hz are listed in the same table.

SystemVL ÷ √3IEC 60038
120/208 V120.1 V60 Hz
230/400 V230.9 V50 Hz and 60 Hz
240/415 V239.6 VOlder value; IEC 60038 notes these systems still exist
277/480 V277.1 V60 Hz
347/600 V346.4 V60 Hz
400/690 V398.4 V50 Hz

Where the simple formulas stop working

  • Unbalanced loads. Single-phase loads spread across a star supply rarely match. Calculate each phase separately and add the powers; the neutral carries what is left over.
  • Nonlinear loads. Drives and rectifiers draw harmonic current. With distortion, P ÷ S is no longer cos φ, and in a star system with single-phase rectifiers the neutral can carry significant current even when balanced.
  • Motors. The calculated current is the running current at that output. Use the nameplate and your electrical code tables for conductor and overload sizing, and allow for starting inrush, which this calculation does not include.
  • Voltage is nominal. Real supplies vary; a constant-power load draws more current when the voltage sags, and a resistive heater draws less power.

Glossary

Line voltage (VL)
The RMS voltage between any two of the three lines, also called line-to-line voltage.
Phase voltage (Vph)
The voltage across one element of the load or source: VL ÷ √3 in star and VL in delta.
Line current (IL)
The RMS current in each of the three supply conductors.
Phase current (Iph)
The current through one element: IL in star and IL ÷ √3 in delta.
Star (wye)
Three elements joined at a common neutral point, each from a line to neutral.
Delta
Three elements in a closed triangle, each between two lines.
Balanced load
All three phases have the same impedance, so the phase currents are equal in size and 120° apart.
Power factor
Real power divided by apparent power, equal to cos φ for sinusoidal waveforms.

Related guides

Frequently asked questions

What is the three-phase power formula?

P = √3 × VL × IL × PF, with VL the line-to-line voltage, IL the line current and PF the power factor. Apparent power is S = √3 × VL × IL and reactive power is Q = √(S² − P²). All three are totals for the three phases.

How do I convert kW to amps on a three-phase system?

I = P ÷ (√3 × VL × PF). A 10 kW load at 400 V and PF 0.85 draws 16.98 A per line. Motors also need the efficiency: divide shaft kW by efficiency first to get the electrical input.

How do I convert kVA to amps on a three-phase system?

I = S ÷ (√3 × VL). A 75 kVA transformer at 480 V is rated 90.21 A per line. Power factor does not enter, because kVA already includes the reactive part.

How do I get kW from amps on a three-phase system?

kW = √3 × VL × IL × PF ÷ 1000, with VL the line-to-line voltage and IL the line current. At 480 V, 100 A and PF 0.85 that is 70.7 kW.

Why is there a √3 in three-phase power?

The voltage between two lines is the difference of two sine waves 120° apart, which is √3 times one line-to-neutral voltage. Total power is three times the per-phase power, and 3 × (VL ÷ √3) × IL simplifies to √3 × VL × IL.

What is the difference between star and delta?

In star (wye) each element connects from a line to the neutral point, so it sees VL ÷ √3 and carries the line current. In delta each element connects between two lines, so it sees the full VL and carries IL ÷ √3.

Does star or delta give more power?

With the same three elements on the same supply, delta draws three times the power and three times the line current. Three 10 Ω heaters at 400 V give 16 kW in star and 48 kW in delta. For a stated load with given line values, the total power is the same either way.

What is the line-to-neutral voltage of a 208 V or 480 V system?

Divide by √3: 208 V gives 120.1 V and 480 V gives 277.1 V, which is why these systems are written 120/208 V and 277/480 V.

How do I handle an unbalanced three-phase load?

The √3 formulas in this three-phase power calculator assume all three phases carry the same load. For an unbalanced load, calculate V × I × PF for each phase using its own line-to-neutral voltage and current, and add the three results. The neutral then carries the imbalance current.