This 4-20 mA calculator converts loop current to percent and engineering units and back, sizes the receiver resistor for your ADC, and checks that the loop has enough voltage. It also reports the signal state from the NAMUR NE 43 levels that transmitter manuals publish.

Calculate
Examples
mA
Ω

The burden resistor the loop current flows through.

Value

5 bar

Percent of span
50 %
Signal state (NE 43)
In range (4 to 20 mA)
Voltage across 250 Ω
3 V
Resistor power
36 mW
Value against loop current
-20246810125101520Loop current (mA)Value (bar)4 mA20 mA12 mA

Scale points

PercentCurrentValueAcross 250 Ω
0 %4 mA0 bar1 V
25 %8 mA2.5 bar2 V
50 %12 mA5 bar3 V
75 %16 mA7.5 bar4 V
100 %20 mA10 bar5 V

How do you convert 4-20 mA to engineering units?

Value = low + (high − low) × (I − 4) ÷ 16. On a 0 to 10 bar range, 12 mA is 5 bar (50 %). A 250 Ω receiver turns 4-20 mA into 1 V to 5 V, and the loop needs at least the transmitter’s minimum voltage plus 20 mA times the total loop resistance.

4-20 mA scaling formula and loop equations

The 4-20 mA formula is a straight line from 4 mA at the bottom of the range to 20 mA at the top, so the 4-20 mA scaling calculator above only needs the two end values. Everything else is Ohm’s law around a series loop.

V = L + (H − L) × (I − 4) ÷ 16     I = 4 + 16 × (V − L) ÷ (H − L)
I
loop current in mA
L, H
the values at 4 mA and at 20 mA
V
the measured value in engineering units

The receiver resistor is chosen for the voltage you want at the design current:

R = Vtarget ÷ Idesign     Vrx = I × R

The loop only works if the supply covers the transmitter’s minimum voltage, any other series drops and the drop across all the resistance in the loop:

Rmax = (Vsupply − Vtx,min − Vother) ÷ I     Vsupply(min) = Vtx,min + Vother + I × Rloop
Vtx,min
minimum transmitter terminal voltage
Vother
barriers, diodes, loop-powered displays
Rloop
receiver resistor plus round-trip wire resistance

Check this at the highest current the transmitter can drive, not only at 20 mA. Endress+Hauser and Rosemount both publish load limits equivalent to about 23 mA, the top of their alarm range.

How to calculate 4-20 mA signal scaling and loop budget

Example 1: 12 mA on a 0 to 10 bar transmitter

(12 − 4) ÷ 16 = 50 % of span, so the value is 5 bar. Across a 250 Ω receiver that is 3 V.

Example 2: 25 °C on a −50 to 150 °C transmitter

I = 4 + 16 × (25 − (−50)) ÷ 200 = 10 mA, which is 37.5 % of span. Negative range values are handled the same way: only the difference between them matters.

Example 3: loop budget for a 10.5 V transmitter from 24 V

A 250 Ω receiver plus 10 Ω of wire makes 260 Ω. The limit is (24 − 10.5) ÷ 20 mA = 675 Ω at 20 mA and 587 Ω at 23 mA, so the loop fits with room to spare. It needs at least 15.7 V at 20 mA, and the transmitter sees 18.8 V at that current.

4-20 mA conversion table

Percent of span against loop current, with the voltage across a 250 Ω receiver and a 165 Ω receiver.

PercentCurrentAcross 250 ΩAcross 165 Ω
0 %4 mA1 V660 mV
10 %5.6 mA1.4 V924 mV
25 %8 mA2 V1.32 V
50 %12 mA3 V1.98 V
75 %16 mA4 V2.64 V
90 %18.4 mA4.6 V3.036 V
100 %20 mA5 V3.3 V

NAMUR NE 43 signal levels

As published by Endress+Hauser and in Rosemount’s NAMUR option. The NE 43 text is sold by NAMUR, so check your device’s manual: alarm levels are configurable.

CurrentMeaningWhat the receiver should do
≤ 3.6 mAFailure, lowTreat as invalid; near 0 mA usually means an open loop
3.6 to 3.8 mANot defined as a measurementCheck thresholds in the device manual
3.8 to 4 mAUnder-rangeValid measurement, past the bottom of the range
4 to 20 mAMeasuring rangeNormal
20 to 20.5 mAOver-rangeValid measurement, past the top of the range
20.5 to 21 mANot defined as a measurementCheck thresholds in the device manual
≥ 21 mAFailure, highTreat as invalid (Rosemount’s NAMUR option alarms at ≥ 22.5 mA)

Maximum loop resistance by supply voltage

For a transmitter with a 10.5 V minimum, at 20 mA and at the 23 mA that vendors use for their load limits. For your own transmitter, use the current loop calculator on the Loop compliance tab.

SupplyAt 20 mAAt 23 mA
12 V75 Ω65.22 Ω
15 V225 Ω195.7 Ω
18 V375 Ω326.1 Ω
24 V675 Ω587 Ω
30 V975 Ω847.8 Ω
36 V1.275 kΩ1.109 kΩ

Receiver resistors for common ADC ranges

The E96 value at or below ADC range ÷ 20 mA, so that 20 mA stays inside the range. For other ranges, use the 4-20 mA resistor calculator on the Receiver resistor tab.

ADC rangeE96 resistorAt 4 mAAt 20 mA
2.048 V102 Ω408 mV2.04 V
2.5 V124 Ω496 mV2.48 V
3.3 V165 Ω660 mV3.3 V
5 V249 Ω996 mV4.98 V
10 V499 Ω1.996 V9.98 V

What goes wrong in real circuits

Running out of compliance voltage is the classic fault. The transmitter reads correctly at 4 mA and then flattens off as the current rises, so test the loop at full scale and at the alarm current, not only in the middle. Size the receiver resistor with care too: if the reading must detect a high alarm, 20 mA cannot be at the top of the ADC range, because a 21 mA failure would simply clip and look like a maximum reading. The receiver resistor is a direct gain error, so use a 0.1 % or better part. Protect the input as well: a shorted transmitter can put the whole supply across the receiver, which at 24 V is 2.3 W in a 250 Ω resistor. Finally, keep track of grounding, because one wire of a receiver resistor at the ground of an ADC ties the loop to that ground, and two grounded points in one loop create a path for error currents.

Glossary

Live zero
A signal range whose zero is above 0 mA, so a dead loop can be told apart from a zero reading.
Span
The change across the range. 4-20 mA has a 16 mA span.
Receiver (burden) resistor
The resistor that converts the loop current into a voltage for an ADC or controller input.
Compliance
The voltage a transmitter needs across its terminals to keep regulating the loop current.
Two-wire transmitter
A transmitter powered by the same pair of wires that carries its 4-20 mA signal.
NE 43
The NAMUR recommendation that standardizes how digital transmitters signal failures on the analog current.
HART
A digital signal superimposed on the 4-20 mA current, used to configure and read smart transmitters.

Related guides

Frequently asked questions

What is the 4-20 mA conversion formula?

Value = low + (high − low) × (I − 4) ÷ 16. On a 0 to 10 bar transmitter, 12 mA is 5 bar, or 50 % of span.

What resistor converts 4-20 mA to 1-5 V?

250 Ω. Ohm’s law gives 1 V at 4 mA and 5 V at 20 mA. For a 3.3 V ADC, 165 Ω gives 660 mV to 3.3 V.

How do you calculate the maximum loop resistance?

Rmax = (Vsupply − Vtransmitter,min) ÷ I. With 24 V and a 10.5 V transmitter that is 675 Ω at 20 mA. Vendors such as Endress+Hauser and Rosemount evaluate it near the alarm current: Rosemount’s formula, 43.5 × (V − 10.5), corresponds to 23 mA and gives about 587 Ω.

What do NAMUR NE 43 current levels mean?

Device documentation that follows NE 43 treats 3.8 to 20.5 mA as a measurement, with 3.8 to 4 mA and 20 to 20.5 mA as under-range and over-range, and ≤ 3.6 mA or ≥ 21 mA as a failure signal. NE 43 was revised in 2021 and the exact alarm level varies by device, so check its manual.

Why does 4-20 mA start at 4 mA and not 0?

The live zero lets the receiver tell a true zero reading (4 mA) from a broken wire or dead transmitter (near 0 mA), and it leaves a few milliamps to power a two-wire transmitter from the loop itself.

Does wire length affect a 4-20 mA signal?

Not the reading, as long as the loop closes: the current is the same everywhere in a series loop. Wire resistance only uses up compliance voltage. At 20 mA, every 100 Ω of round-trip wire costs 2 V.

What resistance does a HART 4-20 mA loop need?