What is the 4-20 mA conversion formula?
Value = low + (high − low) × (I − 4) ÷ 16. On a 0 to 10 bar transmitter, 12 mA is 5 bar, or 50 % of span.
This 4-20 mA calculator converts loop current to percent and engineering units and back, sizes the receiver resistor for your ADC, and checks that the loop has enough voltage. It also reports the signal state from the NAMUR NE 43 levels that transmitter manuals publish.
The burden resistor the loop current flows through.
Value
5 bar
Scale points
| Percent | Current | Value | Across 250 Ω |
|---|---|---|---|
| 0 % | 4 mA | 0 bar | 1 V |
| 25 % | 8 mA | 2.5 bar | 2 V |
| 50 % | 12 mA | 5 bar | 3 V |
| 75 % | 16 mA | 7.5 bar | 4 V |
| 100 % | 20 mA | 10 bar | 5 V |
Value = low + (high − low) × (I − 4) ÷ 16. On a 0 to 10 bar range, 12 mA is 5 bar (50 %). A 250 Ω receiver turns 4-20 mA into 1 V to 5 V, and the loop needs at least the transmitter’s minimum voltage plus 20 mA times the total loop resistance.
The 4-20 mA formula is a straight line from 4 mA at the bottom of the range to 20 mA at the top, so the 4-20 mA scaling calculator above only needs the two end values. Everything else is Ohm’s law around a series loop.
The receiver resistor is chosen for the voltage you want at the design current:
The loop only works if the supply covers the transmitter’s minimum voltage, any other series drops and the drop across all the resistance in the loop:
Check this at the highest current the transmitter can drive, not only at 20 mA. Endress+Hauser and Rosemount both publish load limits equivalent to about 23 mA, the top of their alarm range.
(12 − 4) ÷ 16 = 50 % of span, so the value is 5 bar. Across a 250 Ω receiver that is 3 V.
I = 4 + 16 × (25 − (−50)) ÷ 200 = 10 mA, which is 37.5 % of span. Negative range values are handled the same way: only the difference between them matters.
A 250 Ω receiver plus 10 Ω of wire makes 260 Ω. The limit is (24 − 10.5) ÷ 20 mA = 675 Ω at 20 mA and 587 Ω at 23 mA, so the loop fits with room to spare. It needs at least 15.7 V at 20 mA, and the transmitter sees 18.8 V at that current.
Percent of span against loop current, with the voltage across a 250 Ω receiver and a 165 Ω receiver.
| Percent | Current | Across 250 Ω | Across 165 Ω |
|---|---|---|---|
| 0 % | 4 mA | 1 V | 660 mV |
| 10 % | 5.6 mA | 1.4 V | 924 mV |
| 25 % | 8 mA | 2 V | 1.32 V |
| 50 % | 12 mA | 3 V | 1.98 V |
| 75 % | 16 mA | 4 V | 2.64 V |
| 90 % | 18.4 mA | 4.6 V | 3.036 V |
| 100 % | 20 mA | 5 V | 3.3 V |
As published by Endress+Hauser and in Rosemount’s NAMUR option. The NE 43 text is sold by NAMUR, so check your device’s manual: alarm levels are configurable.
| Current | Meaning | What the receiver should do |
|---|---|---|
| ≤ 3.6 mA | Failure, low | Treat as invalid; near 0 mA usually means an open loop |
| 3.6 to 3.8 mA | Not defined as a measurement | Check thresholds in the device manual |
| 3.8 to 4 mA | Under-range | Valid measurement, past the bottom of the range |
| 4 to 20 mA | Measuring range | Normal |
| 20 to 20.5 mA | Over-range | Valid measurement, past the top of the range |
| 20.5 to 21 mA | Not defined as a measurement | Check thresholds in the device manual |
| ≥ 21 mA | Failure, high | Treat as invalid (Rosemount’s NAMUR option alarms at ≥ 22.5 mA) |
For a transmitter with a 10.5 V minimum, at 20 mA and at the 23 mA that vendors use for their load limits. For your own transmitter, use the current loop calculator on the Loop compliance tab.
| Supply | At 20 mA | At 23 mA |
|---|---|---|
| 12 V | 75 Ω | 65.22 Ω |
| 15 V | 225 Ω | 195.7 Ω |
| 18 V | 375 Ω | 326.1 Ω |
| 24 V | 675 Ω | 587 Ω |
| 30 V | 975 Ω | 847.8 Ω |
| 36 V | 1.275 kΩ | 1.109 kΩ |
The E96 value at or below ADC range ÷ 20 mA, so that 20 mA stays inside the range. For other ranges, use the 4-20 mA resistor calculator on the Receiver resistor tab.
| ADC range | E96 resistor | At 4 mA | At 20 mA |
|---|---|---|---|
| 2.048 V | 102 Ω | 408 mV | 2.04 V |
| 2.5 V | 124 Ω | 496 mV | 2.48 V |
| 3.3 V | 165 Ω | 660 mV | 3.3 V |
| 5 V | 249 Ω | 996 mV | 4.98 V |
| 10 V | 499 Ω | 1.996 V | 9.98 V |
Running out of compliance voltage is the classic fault. The transmitter reads correctly at 4 mA and then flattens off as the current rises, so test the loop at full scale and at the alarm current, not only in the middle. Size the receiver resistor with care too: if the reading must detect a high alarm, 20 mA cannot be at the top of the ADC range, because a 21 mA failure would simply clip and look like a maximum reading. The receiver resistor is a direct gain error, so use a 0.1 % or better part. Protect the input as well: a shorted transmitter can put the whole supply across the receiver, which at 24 V is 2.3 W in a 250 Ω resistor. Finally, keep track of grounding, because one wire of a receiver resistor at the ground of an ADC ties the loop to that ground, and two grounded points in one loop create a path for error currents.
Value = low + (high − low) × (I − 4) ÷ 16. On a 0 to 10 bar transmitter, 12 mA is 5 bar, or 50 % of span.
250 Ω. Ohm’s law gives 1 V at 4 mA and 5 V at 20 mA. For a 3.3 V ADC, 165 Ω gives 660 mV to 3.3 V.
Rmax = (Vsupply − Vtransmitter,min) ÷ I. With 24 V and a 10.5 V transmitter that is 675 Ω at 20 mA. Vendors such as Endress+Hauser and Rosemount evaluate it near the alarm current: Rosemount’s formula, 43.5 × (V − 10.5), corresponds to 23 mA and gives about 587 Ω.
Device documentation that follows NE 43 treats 3.8 to 20.5 mA as a measurement, with 3.8 to 4 mA and 20 to 20.5 mA as under-range and over-range, and ≤ 3.6 mA or ≥ 21 mA as a failure signal. NE 43 was revised in 2021 and the exact alarm level varies by device, so check its manual.
The live zero lets the receiver tell a true zero reading (4 mA) from a broken wire or dead transmitter (near 0 mA), and it leaves a few milliamps to power a two-wire transmitter from the loop itself.
Not the reading, as long as the loop closes: the current is the same everywhere in a series loop. Wire resistance only uses up compliance voltage. At 20 mA, every 100 Ω of round-trip wire costs 2 V.
Rosemount specifies a minimum loop resistance of 250 Ω for HART communication, which is one reason 250 Ω is such a common receiver value.