From a material, a length and an AWG size or diameter, this wire resistance calculator finds the DC resistance, corrected for temperature. It also solves for the length that gives a target resistance and the thinnest gauge that stays under one.

Solve for
Examples
Wire size given as

One-way conductor length. Double it for a go-and-return run.

Length unit
°C
A

Optional: voltage drop and power in the wire.

Resistance at 20 °C

842.1 mΩ

Resistance at 20 °C
842.1 mΩ
Temperature factor R(T) / R(20 °C)
1
Resistivity at 20 °C
17.24 nΩ·m
Resistance per meter
84.21 mΩ/m
Resistance per 1000 ft
25.67 Ω
Diameter
0.5106 mm
Cross-section
0.2047 mm²

DC resistance of a solid round wire. A stranded conductor measures about 2 % higher for the same cross-section (NBS Handbook 100, for sizes up to 2,000,000 circular mils, about 1000 mm²), and at high frequency skin effect raises the resistance further.

Resistance versus temperature
600m800m11.21.41.6-50050100150200Temperature (°C)Resistance (Ω)20 °C

Same wire in other materials

MaterialR at 20 °CR at 20 °C
Copper, annealed (100 % IACS)842.1 mΩ842.1 mΩ
Aluminum, hard-drawn (61 % IACS)1.381 Ω1.381 Ω
Silver, pure annealed775.6 mΩ775.6 mΩ
Gold, pure annealed1.082 Ω1.082 Ω
Tungsten2.593 Ω2.593 Ω
Nichrome 80/20 (Nikrothal 80)53.24 Ω53.24 Ω
Constantan (CuNi44, ISOTAN)23.93 Ω23.93 Ω

How do you calculate wire resistance?

Use R = ρL ÷ A, then correct for temperature. 10 m of 24 AWG copper (ρ = 1.7241 × 10⁻⁸ Ω·m, A = 0.2047 mm²) is 842.1 mΩ at 20 °C. Copper gains 0.393 % per °C, so the same wire is 1.057 Ω at 85 °C.

Wire resistance formula

Resistance grows with length and shrinks with cross-section. The material sets the resistivity, and temperature moves it.

R = ρ(T) × L ÷ A
R
resistance in Ω
ρ(T)
resistivity of the material at temperature T, in Ω·m
L
conductor length in m (double it for a go-and-return run)
A
cross-section in m²; for a round wire A = π d² ÷ 4

Copper and aluminum add a straight-line temperature correction to the wire resistance equation, taken from their standards:

ρ(T) = ρ20 × (1 + α20 × (T − 20 °C))
ρ20
resistivity at 20 °C
α20
0.00393 per °C for annealed copper, 0.00403 per °C for hard-drawn aluminum

Silver and gold are interpolated from the Matula recommended tables, tungsten uses the White and Minges polynomial, and nichrome uses the Kanthal temperature factor, because none of those is a single straight line over its working range. The AWG diameter follows the definition of the gauge:

d = 0.127 mm × 92^((36 − n) ÷ 39)
n
gauge number; 00, 000 and 0000 are −1, −2 and −3

How to calculate wire resistance: worked examples

Example 1: 10 m of 24 AWG hookup wire

d = 0.5106 mm, so A = 0.2047 mm². R = 1.7241 × 10⁻⁸ × 10 ÷ (0.2047 × 10⁻⁶) = 842.1 mΩ at 20 °C. At 85 °C the factor is 1 + 0.00393 × 65 = 1.255, giving 1.057 Ω.

Example 2: copper versus aluminum, 25 mm², 50 m, at 40 °C

Copper: 37.19 mΩ. Hard-drawn aluminum: 61.08 mΩ, 1.64 times as much. Aluminum also has the slightly larger coefficient, 0.00403 per °C.

Example 3: a 20 Ω nichrome heater from 0.5 mm wire, running at 400 °C

A = 0.1963 mm² and Ct at 400 °C is 1.04, so ρ = 1.134 µΩ·m. L = R × A ÷ ρ = 3.464 m. Cold, the same element measures 19.23 Ω.

Resistivity of common wire materials

Values at 20 °C from the sources listed below. The coefficient is the mean between 20 °C and 100 °C, for comparison.

Materialρ at 20 °CµΩ·cmMean α (per °C)Basis
Copper, annealed (100 % IACS)17.24 nΩ·m1.7240.00393International Annealed Copper Standard
Aluminum, hard-drawn (61 % IACS)28.26 nΩ·m2.8260.00403IS 398 Part 1 (maximum resistivity)
Silver, pure annealed15.88 nΩ·m1.5880.00383Matula 1979, 99.999 % metal
Gold, pure annealed22.15 nΩ·m2.2150.00375Matula 1979, 99.999 % metal
Tungsten53.1 nΩ·m5.310.0045White and Minges fit, 100 to 3600 K
Nichrome 80/20 (Nikrothal 80)1.09 µΩ·m1090.000125Kanthal Nikrothal 80 datasheet
Constantan (CuNi44, ISOTAN)490 nΩ·m49about 0Isabellenhütte ISOTAN datasheet

AWG resistance chart: copper wire at 20 °C

This copper wire resistance chart is computed from the exact geometric diameter and the annealed copper standard. Printed tables round small diameters to 0.1 mil, so for gauges thinner than about 30 AWG they can differ from these values by up to about 3 %: NBS Handbook 100 lists 1080 Ω per 1000 ft for 40 AWG.

AWGDiameterAreamΩ per mΩ per 1000 ft
000011.68 mm107.2 mm²0.16080.04901
009.266 mm67.43 mm²0.25570.07793
08.251 mm53.48 mm²0.32240.09827
26.544 mm33.63 mm²0.51270.1563
45.189 mm21.15 mm²0.81520.2485
64.115 mm13.3 mm²1.2960.3951
83.264 mm8.366 mm²2.0610.6282
102.588 mm5.261 mm²3.2770.9988
122.053 mm3.309 mm²5.2111.588
141.628 mm2.081 mm²8.2852.525
161.291 mm1.309 mm²13.174.015
181.024 mm0.823 mm²20.956.385
200.8118 mm0.5176 mm²33.3110.15
220.6438 mm0.3255 mm²52.9616.14
240.5106 mm0.2047 mm²84.2125.67
260.4049 mm0.1288 mm²133.940.81
280.3211 mm0.08098 mm²212.964.9
300.2546 mm0.05093 mm²338.5103.2
320.2019 mm0.03203 mm²538.3164.1
360.127 mm0.01267 mm²1361414.8
400.07987 mm0.00501 mm²34411049

Wire resistance vs temperature: factor by material

Multiply the 20 °C resistance by these factors. Blank cells are outside the published data for that material.

Material−40 °C0 °C25 °C50 °C75 °C100 °C150 °C200 °C
Copper, annealed (100 % IACS)0.7640.9211.0201.1181.2161.3141.5111.707
Aluminum, hard-drawn (61 % IACS)0.7580.9191.0201.1211.2221.3221.5241.725
Silver, pure annealed0.7730.9241.0191.1141.2101.3071.5041.703
Gold, pure annealed0.7800.9261.0181.1121.2051.3001.4931.689
Tungsten0.7400.9121.0221.1331.2461.3601.5921.830
Nichrome 80/20 (Nikrothal 80)1.0011.0041.0071.0101.0151.020
Constantan (CuNi44, ISOTAN)1.0001.0001.0001.0001.0001.000

Where the model stops

This is the DC resistance of one solid round conductor. Use the conductor temperature, not the room temperature: a loaded cable runs hotter than its surroundings, and that raises its resistance and its losses together. Stranded conductors read about 2 % high, and enameled, tinned or plated wire can differ from the base metal. Alloy resistance wire is sold to a tolerance (ISOTAN is ±10 % on resistivity), so measure a sample if the value matters. Terminations often add more resistance than a short length of wire, so use a four-wire measurement on anything below about 1 Ω.

Glossary

Resistivity (ρ)
The resistance of a unit cube of a material, in Ω·m. It depends on the material and the temperature, not on the shape.
Temperature coefficient (α)
The fractional change in resistance per °C, quoted at a reference temperature, here 20 °C.
IACS
International Annealed Copper Standard: the 1913 reference that defines 100 % conductivity as 1/58 Ω·mm²/m at 20 °C.
AWG
American Wire Gauge. A geometric series of 39 steps between 0.0050 in (36 AWG) and 0.4600 in (0000 AWG).
Temperature factor (Ct)
Ratio of resistance at temperature T to resistance at 20 °C, as heating-alloy datasheets publish it.

Related guides

Frequently asked questions

How do you calculate the resistance of a wire?

Multiply the resistivity by the length and divide by the cross-section: R = ρL / A. Then correct for temperature, which for copper means multiplying by 1 + 0.00393 × (T − 20 °C).

What is the resistance of 24 AWG copper wire?

84.21 mΩ per meter at 20 °C, or 25.67 Ω per 1000 ft. Ten meters is 842.1 mΩ.

What is copper wire resistance per foot?

It depends on the gauge. 24 AWG at 20 °C is 0.02567 Ω per foot, or 84.21 mΩ per meter. The AWG resistance chart on this page lists other gauges.

Can I use this as a cable resistance calculator?

Yes. Treat each conductor as one wire and double the length for a go-and-return run. Stranded conductors read about 2 % higher than a solid wire of the same total cross-section.

How much does copper resistance increase with temperature?

About 0.39 % per °C around room temperature. Going from 20 °C to 100 °C raises it by 31.4 %. NBS Handbook 100 treats the curve as linear up to 200 °C.

How much higher is aluminum resistance than copper?

1.64 times the copper value for the same cross-section, because hard-drawn aluminum is 61 % of the conductivity of annealed copper. An aluminum conductor needs about 1.64 times the area to match.

Why do resistivity tables list different values for copper?

Wire tables use the International Annealed Copper Standard, 1.7241 × 10⁻⁸ Ω·m at 20 °C, which is a defined reference for commercial wire. Physics handbooks list pure annealed copper, 1.678 × 10⁻⁸ Ω·m at 293 K, which is 2.7 % lower. This calculator uses the wire standard.

Does stranded wire have higher resistance than solid wire?

Slightly. NBS Handbook 100 uses 2 % more resistance than a solid rod of the same total cross-section for sizes up to 2,000,000 circular mils (about 1000 mm²), rising to 5 % for the largest conductors, because each strand follows a longer helical path.

What is the resistivity of nichrome wire?

1.09 µΩ·m at 20 °C for Kanthal Nikrothal 80, about 63 times copper. It rises only 4 % by 400 °C, so a heater holds nearly the same resistance hot as cold.

Does AC change the resistance of a wire?

Yes, at high enough frequency. Skin effect pushes the current toward the surface and reduces the effective cross-section. This calculator gives the DC value, which is also the mains-frequency value for small conductors.