How do I read a Pt100 chart?
Each row is a starting temperature and each column adds to it, so row −100 and column +30 is −70 °C, where a Pt100 reads 72.33 Ω. For a temperature between the 10 °C steps, enter it in the calculator above.
Convert temperature to resistance and back for Pt100, Pt1000 and other platinum RTDs with the IEC 60751 Callendar-Van Dusen equation, or read common values off the Pt100 chart below. The calculator also shows the sensitivity at any point and the tolerance for classes AA, A, B and C.
Sets the range each class is valid over.
Resistance at 100.00 °C
138.5055 Ω
Standard IEC 60751 curve (α = 0.00385). Tolerance covers the sensor only: add lead resistance, self-heating and measurement-circuit errors.
Tolerance at 100.0 °C for a thin-film element
| Class | ± °C | ± Ω | Valid range | In range |
|---|---|---|---|---|
| AA | 0.270 | 0.102 | 0 to 150 °C | Yes |
| A | 0.350 | 0.133 | -30 to 300 °C | Yes |
| B | 0.800 | 0.303 | -50 to 500 °C | Yes |
| C | 1.600 | 0.607 | -50 to 600 °C | Yes |
Above 0 °C, use R = R0 (1 + At + Bt²) with A = 3.9083 × 10⁻³ and B = −5.775 × 10⁻⁷. A Pt100 (R0 = 100 Ω) at 100 °C is 138.51 Ω, and it changes by 0.379 Ω per °C at that point. Below 0 °C the equation adds the term Ct³(t − 100), and a Pt1000 is exactly ten times the Pt100 value.
IEC 60751 defines the resistance of an industrial platinum RTD with the Callendar-Van Dusen equation. The two ranges share A and B, and the C term only applies below 0 °C.
Above 0 °C the inverse has a closed form. With x = R ÷ R0, the root is written so that it stays accurate close to 0 °C:
Below 0 °C there is no simple rearrangement, so the calculator solves the quartic numerically. The sensitivity is the derivative of the same equation:
At = 0.39083 and Bt² = −0.005775, so R = 100 × (1 + 0.39083 − 0.005775) = 138.5055 Ω. The sensitivity there is 0.3793 Ω/°C, lower than the 0.3908 Ω/°C at 0 °C because B is negative.
842 Ω is below R0, so the temperature is under 0 °C and the quartic applies. Solving it gives −40.18 °C. Substituting that temperature back returns 842.000 Ω, which confirms the result.
A two-wire Pt100 reads 110 Ω through leads totaling 1 Ω. Ignoring the leads gives 25.68 °C, while the sensor itself is at 109 Ω, or 23.11 °C: an error of 2.6 °C. The same leads on a Pt1000 reading 1100 Ω give an error of 0.26 °C.
An RTD resistance chart from the IEC 60751 equation, every 10 °C. The temperature of a cell is its row plus its column, so row −100 and column 30 is −70 °C.
| °C | +0 | +10 | +20 | +30 | +40 | +50 | +60 | +70 | +80 | +90 |
|---|---|---|---|---|---|---|---|---|---|---|
| −200 | 18.52 | 22.83 | 27.10 | 31.34 | 35.54 | 39.72 | 43.88 | 48.00 | 52.11 | 56.19 |
| −100 | 60.26 | 64.30 | 68.33 | 72.33 | 76.33 | 80.31 | 84.27 | 88.22 | 92.16 | 96.09 |
| 0 | 100.00 | 103.90 | 107.79 | 111.67 | 115.54 | 119.40 | 123.24 | 127.08 | 130.90 | 134.71 |
| 100 | 138.51 | 142.29 | 146.07 | 149.83 | 153.58 | 157.33 | 161.05 | 164.77 | 168.48 | 172.17 |
| 200 | 175.86 | 179.53 | 183.19 | 186.84 | 190.47 | 194.10 | 197.71 | 201.31 | 204.90 | 208.48 |
| 300 | 212.05 | 215.61 | 219.15 | 222.68 | 226.21 | 229.72 | 233.21 | 236.70 | 240.18 | 243.64 |
| 400 | 247.09 | 250.53 | 253.96 | 257.38 | 260.78 | 264.18 | 267.56 | 270.93 | 274.29 | 277.64 |
| 500 | 280.98 | 284.30 | 287.62 | 290.92 | 294.21 | 297.49 | 300.75 | 304.01 | 307.25 | 310.49 |
| 600 | 313.71 | 316.92 | 320.12 | 323.30 | 326.48 | 329.64 | 332.79 | 335.93 | 339.06 | 342.18 |
| 700 | 345.28 | 348.38 | 351.46 | 354.53 | 357.59 | 360.64 | 363.67 | 366.70 | 369.71 | 372.71 |
| 800 | 375.70 | 378.68 | 381.65 | 384.60 | 387.55 | 390.48 | — | — | — | — |
The same curve with R0 = 1000 Ω. Every value is ten times the Pt100 value.
| °C | +0 | +10 | +20 | +30 | +40 | +50 | +60 | +70 | +80 | +90 |
|---|---|---|---|---|---|---|---|---|---|---|
| −200 | 185.20 | 228.25 | 270.96 | 313.35 | 355.43 | 397.23 | 438.76 | 480.05 | 521.10 | 561.93 |
| −100 | 602.56 | 643.00 | 683.25 | 723.35 | 763.28 | 803.06 | 842.71 | 882.22 | 921.60 | 960.86 |
| 0 | 1000.00 | 1039.03 | 1077.93 | 1116.73 | 1155.41 | 1193.97 | 1232.42 | 1270.75 | 1308.97 | 1347.07 |
| 100 | 1385.05 | 1422.93 | 1460.68 | 1498.32 | 1535.84 | 1573.25 | 1610.54 | 1647.72 | 1684.78 | 1721.73 |
| 200 | 1758.56 | 1795.28 | 1831.88 | 1868.36 | 1904.73 | 1940.98 | 1977.12 | 2013.14 | 2049.05 | 2084.84 |
| 300 | 2120.51 | 2156.08 | 2191.52 | 2226.85 | 2262.06 | 2297.16 | 2332.14 | 2367.01 | 2401.76 | 2436.40 |
| 400 | 2470.92 | 2505.33 | 2539.61 | 2573.79 | 2607.85 | 2641.79 | 2675.62 | 2709.33 | 2742.93 | 2776.41 |
| 500 | 2809.78 | 2843.03 | 2876.16 | 2909.18 | 2942.08 | 2974.87 | 3007.54 | 3040.10 | 3072.54 | 3104.87 |
| 600 | 3137.08 | 3169.18 | 3201.15 | 3233.02 | 3264.77 | 3296.40 | 3327.92 | 3359.32 | 3390.61 | 3421.78 |
| 700 | 3452.84 | 3483.78 | 3514.60 | 3545.31 | 3575.90 | 3606.38 | 3636.74 | 3666.99 | 3697.12 | 3727.14 |
| 800 | 3757.04 | 3786.83 | 3816.49 | 3846.05 | 3875.49 | 3904.81 | — | — | — | — |
Tolerance formulas are from IEC 60751 as listed by Texas Instruments. The ranges are the IEC 60751:2008 thermometer values quoted by JUMO and Lapp, and for class C by WIKA. The standard is a paid document we did not read directly.
| Class | Tolerance (°C) | ± at 0 °C | ± at 100 °C | ± Ω at 0 °C (Pt100) | Wire-wound range | Thin-film range |
|---|---|---|---|---|---|---|
| AA | ±(0.1 + 0.0017 |t|) | 0.10 °C | 0.27 °C | 0.039 | −50 to 250 °C | 0 to 150 °C |
| A | ±(0.15 + 0.002 |t|) | 0.15 °C | 0.35 °C | 0.059 | −100 to 450 °C | −30 to 300 °C |
| B | ±(0.3 + 0.005 |t|) | 0.30 °C | 0.80 °C | 0.117 | −196 to 600 °C | −50 to 500 °C |
| C | ±(0.6 + 0.01 |t|) | 0.60 °C | 1.60 °C | 0.234 | −196 to 600 °C | −50 to 600 °C |
IEC 60751 was revised again in 2022, and we did not read that edition either. Senmatic's summary of it lists the same four classes, ranges and formulas as this table, but JMS lists tighter class A and B formulas for finished probes under the same edition. Check the 2022 text if your specification names it.
A two-wire connection measures the leads along with the sensor. Copper leads of a few ohms round trip are enough to move a Pt100 reading by several degrees. Three-wire connections cancel the leads if the wires match, and four-wire connections remove them from the measurement. Pt1000 sensors reduce the problem tenfold.
The excitation current heats the element: ΔT = I²R ÷ E, where E is the self-heating coefficient. Texas Instruments gives a typical range of 2.5 mW/°C for small thin-film elements to 65 mW/°C for larger wire-wound ones. At 1 mA, a Pt100 at 0 °C dissipates 0.10 mW, which raises it by 0.040 °C to 0.0015 °C across that range. TI recommends keeping excitation below about 1 mA. The coefficient depends on the medium, so use the figure from the sensor data sheet.
Each row is a starting temperature and each column adds to it, so row −100 and column +30 is −70 °C, where a Pt100 reads 72.33 Ω. For a temperature between the 10 °C steps, enter it in the calculator above.
109.73 Ω. At 0 °C it is exactly 100 Ω, and near room temperature it changes by about 0.388 Ω per °C.
The Callendar-Van Dusen equation: R = R0 (1 + At + Bt²) from 0 to 850 °C, and R = R0 (1 + At + Bt² + Ct³(t − 100)) from −200 to 0 °C, with A = 3.9083 × 10⁻³, B = −5.775 × 10⁻⁷ and C = −4.183 × 10⁻¹².
Above 0 °C, solve the quadratic: t = 2(x − 1) ÷ (A + √(A² + 4B(x − 1))), where x = R ÷ R0. Below 0 °C the equation is a quartic with no simple rearrangement, so firmware usually uses a lookup table and this Pt100 calculator solves it numerically. For example, 110 Ω is 25.68 °C.
R0: 100 Ω against 1000 Ω at 0 °C. A Pt1000 has exactly ten times the resistance and ten times the sensitivity (3.91 Ω/°C at 0 °C against 0.391 Ω/°C), so the same lead resistance causes a tenth of the temperature error.
They set how far a sensor may deviate from the standard curve. Class B allows ±(0.3 + 0.005 |t|) °C, which is ±0.80 °C at 100 °C, and class A allows ±0.35 °C there. Each class only applies over a stated temperature range, which depends on whether the element is wire-wound or thin-film.
In a two-wire connection the leads add directly to the sensor, and each ohm reads as about 2.56 °C at 0 °C. A three-wire or four-wire connection removes most or all of it, and a Pt1000 reduces it by a factor of ten.
It is the average resistance change per ohm per °C between 0 and 100 °C: (R100 − R0) ÷ (100 × R0). The IEC 60751 coefficients give 0.00385055, which is rounded to 0.00385. Sensors built to a different curve have a different α and need their own coefficients.
The IEC 60751 equation runs from −200 to 850 °C, where a Pt100 measures 18.52 Ω to 390.48 Ω. A specific sensor usually covers less: tolerance classes have narrower ranges, especially for thin-film elements.